S&T Heat Exchanger의 Baffle Spacing을 결정하기 위한 요구사항 (TEMA)

 

- TEMA RCB-4.51 : ID1/5 51mm 보다 커야 한다.

- TEMA RCB-4.52 : unsupported tube 길이는 Table에 표기된 값보다 커서는 안된다. 이점을 고려하여 Baffle Spacing을 정해야 한다..

 

 

(TEMA) RCB-4.51

RCB4.5 SPACING OF BAFFLES AND SUPPORT PLATES

 

RCB4.51 MINIMUM SPACING

Segmental baffles normally should not be spaced closer than 1/5 of the shell ID or 2 in. (51

mm), whichever is greater. However, special design considerations may dictate a closer

spacing.

 

 

(TEMA) RCB-4.52

 

RCB-4.52 MAXIMUM SPACING

Tube support plates shall be so spaced that the unsupported tube span does not exceed

the value indicated in Table RCB-4.52 for the tube material used.

 